Low voltage AC drives
ABB industrial drives
ACS880, single drives
0.75 to 1700 hp (0.55 to 1300 kW)
- The all-compatible ACS880 series drives
- How to select a drive
- Technical data
- Wall-mounted single drives, ACS880-01
- Main features
- Ratings, types and voltages (230 V)
- Ratings, types and voltages (500 V)
- Ratings, types and voltages (600 V)
- Dimensions
- Standard interface and extensions for comprehensive connectivity
- Standard software for scalable control and functionality
- Intuitive human-machine interface
- Integrated safety simplifies configuration
- Flexible connectivity to automation networks
- Input/output extension modules for increased connectivity
- Speed feedback interfaces for precise process control
- DDCS communication option modules
Ratings, types and voltages (230 V)
Wall-mounted drives, ACS880-01
UN = 230 V (range 208 to 240 V). The power ratings are valid at nominal voltage 230 V (0.75 to 100 Hp). | ||||||||||||
Nominal Rating |
Light-overload use | Heavy-duty use | Noise level |
Heat dissipation |
Air flow | Type designation | Frame size |
|||||
Imax A |
ILd A |
PLd hp |
PLd kW |
IHd A |
PHd hp |
PHd kW |
dBA | W | cfm | m3/h | ||
6.3 | 4.4 | 1 | 1 | 3.7 | 0.75 | 0.55 | 46 | 73 | 26 | 44 | ACS880-01-04A6-2 | R1 |
7.8 | 6.3 | 1.5 | 1.1 | 4.6 | 1 | 1 | 46 | 94 | 26 | 44 | ACS880-01-06A6-2 | R1 |
11.2 | 7.1 | 2 | 2 | 6.6 | 1.5 | 1.1 | 46 | 122 | 26 | 44 | ACS880-01-07A5-2 | R1 |
12.8 | 10.1 | 3 | 2 | 7.5 | 2 | 2 | 46 | 172 | 26 | 44 | ACS880-01-10A6-2 | R1 |
18 | 16 | 5 | 4 | 10.6 | 3 | 2 | 51 | 232 | 52 | 88 | ACS880-01-16A8-2 | R2 |
28.6 | 23.1 | 7.5 | 5.5 | 16.8 | 5 | 4 | 51 | 337 | 52 | 88 | ACS880-01-24A3-2 | R2 |
41 | 29.3 | 10 | 8 | 24.3 | 7.5 | 5.5 | 57 | 457 | 79 | 134 | ACS880-01-031A-2 | R3 |
64 | 44 | 15 | 11 | 38 | 10 | 8 | 62 | 500 | 79 | 134 | ACS880-01-046A-2 | R4 |
76 | 58 | 20 | 15 | 45 | 15 | 11 | 62 | 630 | 165 | 280 | ACS880-01-061A-2 | R4 |
104 | 71 | 25 | 19 | 61 | 20 | 15 | 62 | 680 | 165 | 280 | ACS880-01-075A-2 | R5 |
122 | 83 | 30 | 22 | 72 | 25 | 19 | 62 | 730 | 165 | 280 | ACS880-01-087A-2 | R5 |
148 | 109 | 40 | 30 | 87 | 30 | 22 | 67 | 840 | 256 | 435 | ACS880-01-115A-2 | R6 |
178 | 138 | 50 | 37 | 105 | 40 | 30 | 67 | 940 | 256 | 435 | ACS880-01-145A-2 | R6 |
247 | 162 | 60 | 45 | 145 | 50 | 37 | 67 | 1260 | 265 | 450 | ACS880-01-170A-2 | R7 |
287 | 196 | 75 | 55 | 169 | 60 | 45 | 67 | 1500 | 265 | 450 | ACS880-01-206A-2 | R7 |
362 | 260 | 100 | 75 | 213 | 75 | 55 | 65 | 2100 | 324 | 220 | ACS880-01-274A-2 | R8 |
Ratings, types and voltages (500 V)
Wall-mounted drives, ACS880-01
UN = 500 V (range 380 to 500 V). The power ratings are valid at nominal voltage 480 V (0.75 to 350 Hp). | ||||||||||||
Nominal Rating |
Light-overload use | Heavy-duty use | Noise level |
Heat dissipation |
Air flow | Type designation | Frame size |
|||||
Imax A |
ILd A |
PLd hp |
PLd kW |
IHd A |
PHd hp |
PHd kW |
dBA | W | cfm | m3/h | ||
3.1 | 2.1 | 1 | 0.75 | 1.7 | 0.75 | 0.55 | 46 | 30 | 26 | 44 | ACS880-01-02A1-5 | R1 |
4.1 | 3 | 1.5 | 1.1 | 2.1 | 1 | 0.75 | 46 | 40 | 26 | 44 | ACS880-01-03A0-5 | R1 |
5.6 | 3.4 | 2 | 1.5 | 3 | 1.5 | 1.1 | 46 | 52 | 26 | 44 | ACS880-01-03A4-5 | R1 |
6.8 | 4.8 | 3 | 2.2 | 3.4 | 2 | 1.5 | 46 | 73 | 26 | 44 | ACS880-01-04A8-5 | R1 |
12.2 | 7.6 | 5 | 4 | 5.2 | 3 | 3 | 46 | 122 | 26 | 44 | ACS880-01-07A6-5 | R1 |
16 | 11 | 7.5 | 5.5 | 7.6 | 5 | 4 | 46 | 172 | 26 | 44 | ACS880-01-11A0-5 | R1 |
21 | 14 | 10 | 7.5 | 11 | 7.5 | 5.5 | 51 | 232 | 52 | 88 | ACS880-01-014A-5 | R2 |
29 | 21 | 15 | 11 | 14 | 10 | 7.5 | 51 | 337 | 52 | 88 | ACS880-01-021A-5 | R2 |
42 | 27 | 20 | 15 | 21 | 15 | 11 | 57 | 457 | 79 | 134 | ACS880-01-027A-5 | R3 |
54 | 34 | 25 | 19 | 27 | 20 | 15 | 57 | 562 | 79 | 134 | ACS880-01-034A-5 | R3 |
64 | 40 | 30 | 22 | 34 | 25 | 18.5 | 62 | 667 | 79 | 280 | ACS880-01-040A-5 | R4 |
76 | 52 | 40 | 30 | 40 | 30 | 22 | 62 | 907 | 165 | 280 | ACS880-01-052A-5 | R4 |
104 | 65 | 50 | 37 | 52 | 40 | 30 | 62 | 1117 | 165 | 280 | ACS880-01-065A-5 | R5 |
122 | 77 | 60 | 45 | 65 | 50 | 37 | 62 | 1120 | 165 | 280 | ACS880-01-077A-5 | R5 |
148 | 96 | 75 | 55 | 77 | 60 | 45 | 67 | 1295 | 256 | 435 | ACS880-01-096A-5 | R6 |
178 | 124 | 100 | 75 | 96 | 75 | 55 | 67 | 1440 | 256 | 435 | ACS880-01-124A-5 | R6 |
247 | 156 | 125 | 90 | 124 | 100 | 75 | 67 | 1940 | 256 | 450 | ACS880-01-156A-5 | R7 |
287 | 180 | 150 | 110 | 156 | 125 | 90 | 67 | 2310 | 256 | 450 | ACS880-01-180A-5 | R7 |
350 | 240 | 200 | 132 | 180 | 150 | 110 | 65 | 3300 | 324 | 550 | ACS880-01-240A-5 | R8 |
498 | 302 | 250 | 187.5 | 240 | 200 | 132 | 68 | 4200 | 677 | 1150 | ACS880-01-302A-5 | R9 |
542 | 361 | 300 | 200 | 302 | 250 | 187.5 | 68 | 4800 | 677 | 1150 | ACS880-01-361A-5 | R9 |
542 | 414 1) | 350 | 250 | 361 2) | 300 | 200 | 68 | 6000 | 677 | 1150 | ACS880-01-414A-5 | R9 |
1) At an ambient temperature of 30°C (86°F), 393A at 40°C (104°F)
2) 125% overload for 1 minute every 5 minutes
Ratings, types and voltages (600 V)
Wall-mounted drives, ACS880-01
UN = 600 V (range 525 to 690 V). The power ratings are valid at nominal voltage 575 V (5 to 250 Hp). | ||||||||||||
Nominal Rating |
Light-overload use | Heavy-duty use | Noise level |
Heat dissipation |
Air flow | Type designation | Frame size |
|||||
Imax A |
ILd A |
PLd hp |
PLd kW |
IHd A |
PHd hp |
PHd kW |
dBA | W | cfm | m3/h | ||
12.2 | 9 | 7.5 | 5.5 | 6.1 | 5 | 4 | 62 | 217 | 165 | 280 | ACS880-01-07A3-7 | R5 |
18 | 11 | 10 | 7.5 | 9 | 7.5 | 5.5 | 62 | 284 | 165 | 280 | ACS880-01-09A8-7 | R5 |
22 | 17 | 15 | 11 | 11 | 10 | 7.5 | 62 | 399 | 165 | 280 | ACS880-01-14A2-7 | R5 |
29 | 22 | 20 | 15 | 17 | 15 | 11 | 62 | 490 | 165 | 280 | ACS880-01-018A-7 | R5 |
44 | 27 | 25 | 18.5 | 22 | 20 | 15 | 62 | 578 | 165 | 280 | ACS880-01-022A-7 | R5 |
54 | 32 | 30 | 22 | 27 | 25 | 18.5 | 62 | 660 | 165 | 280 | ACS880-01-026A-7 | R5 |
64 | 41 | 40 | 30 | 32 | 30 | 22 | 62 | 864 | 165 | 280 | ACS880-01-035A-7 | R5 |
70 | 52 | 50 | 37 | 41 | 40 | 30 | 62 | 998 | 165 | 280 | ACS880-01-042A-7 | R5 |
71 | 52 | 50 | 37 | 41 | 40 | 30 | 62 | 1120 | 165 | 280 | ACS880-01-049A-7 | R5 |
104 | 62 | 60 | 45 | 52 | 50 | 37 | 67 | 1295 | 256 | 435 | ACS880-01-061A-7 | R6 |
124 | 77 | 75 | 55 | 62 | 60 | 45 | 67 | 1440 | 256 | 435 | ACS880-01-084A-7 | R6 |
168 | 99 | 100 | 75 | 77 | 75 | 55 | 67 | 1940 | 265 | 450 | ACS880-01-098A-7 | R7 |
198 | 125 | 125 | 90 | 99 | 100 | 75 | 67 | 2310 | 265 | 450 | ACS880-01-119A-7 | R7 |
250 | 144 | 150 | 110 | 125 | 125 | 90 | 65 | 3300 | 324 | 550 | ACS880-01-142A-7 | R8 |
274 | 200 | 132 | 144 | 150 | 110 | 65 | 3900 | 324 | 550 | ACS880-01-174A-7 | R8 | |
384 | 242 | 250 | 160 | 192 | 200 | 132 | 68 | 4200 | 677 | 1150 | ACS880-01-210A-7 | R9 |
411 | 271 | 200 | 250 | 160 | 68 | 4800 | 677 | 1150 | ACS880-01-271A-7 | R9 |
3) 130% overload for 1 minute every 5 minutes
4) Drive is capable of 192 amps with no overload
5) Power rating is per NEC table 42.1. Drive can be used for a 300 hp 4 pole motor meeting EPAct efficiency standards (NEMA MG 1, table 12-11) if motor full load current does not exceed 271 amps
© Copyright 2015 ABB. All rights reserved.