Saftronics VG10 - Dynamic Torque Vector AC Drive
(Obsolete FINCOR Series 6600)
DC Link Reactor 100 HP and above
Dimensions in inches
| Hp |
Part Number |
Width |
Height |
Depth |
Weight |
Loss [W] |
| 230V VG10 |
| 100 |
SDCR2-75B |
7.87 |
10.63 |
7.09 |
37 |
55 |
| 125 |
SDCR2-90B |
7.09 |
11.02 |
8.46 |
37 |
57 |
| 460V VG10 |
| 100 |
SDCR4-75B |
7.48 |
10.63 |
6.89 |
35 |
58 |
| 125 |
SDCR4-90B |
7.48 |
11.02 |
7.87 |
44 |
64 |
| 150 |
SDCR4-110B |
7.48 |
11.02 |
7.87 |
46 |
73 |
| 200 |
SDCR4-132B |
7.87 |
11.02 |
8.07 |
55 |
84 |
| 250 |
SDCR4-160B |
8.27 |
12.6 |
8.07 |
68 |
90 |
| 300 |
SDCR4-200B |
8.27 |
12.99 |
9.06 |
75 |
126 |
| 350 |
SDCR4-220B |
8.66 |
13.78 |
9.06 |
81 |
131 |
| 400 |
SDCR4-280B |
8.66 |
14.57 |
9.65 |
95 |
133 |
| 450 |
SDCR4-315B |
9.84 |
12.01 |
8.78 |
88 |
150 |
| 500 |
SDCR4-355B |
9.84 |
12.99 |
8.78 |
99 |
205 |
| 600 |
SDCR4-400B |
9.84 |
13.78 |
9.17 |
106 |
215 |
Note:
- VGi0 Drives rated 100 Hp and above are furnished with a DC link reactor. This
reactor must be installed between terminal Pi and P+ prior to commissioning of
the Drive.
- The weight of the DC Link Reactor is not included with that of the Drive.
- DC Link Reactor is provided as open type. Enclosure to be provided by others.
Prices and spec_ications subject to change without notice.
Call for availability of drives,
and freight options.
(815) 725-9696
All prices are subject to
change without notice.
To purchase any Saftronics drives or information,
contact us at:
Phone (815) 725-9696,
Toll Free (866) 492-9888,
Fax (815) 725-9393 or
E-mail info@joliettech.com
|