Environment |
| Ambient Operating Temperature |
-10°C to 40°C (14°F to 104°F) @ 6kHz carrier freq.
-10°C to 50°C (14°F to 122°F) @ 3kHz carrier freq.
For SE Size 4--25HP and all SE Size 5's.
-10°C to 40°C (14°F to 104°F) @ 3kHz carrier freq. |
| Cooling method |
Convection and forced convection, model dependent |
| Humidity |
95% maximum non-condensing at 40°C (104°F) |
| Storage Temperature |
-40°C to 60°C (-40°F to 140°F) -- 12 months Max. |
| Altitude |
Derate the continuous output current by
1% for every 100m (328 ft) above 1000m (3280 ft) to a maximum of 4000m (13,000 ft) |
| Vibration |
Tested in accordance with IEC 68-2-34 and IEC 68-2-36 |
| Mechanical Shock |
Tested in accordance with IEC 68-2-29 |
| Enclosure |
NEMA 1 (IP 21) |
Electromagnetic
Immunity |
In compliance with EN61800-3 and EN50082-2 |
Electromagnetic
Emissions |
In compliance with EN61800-3
second environment, without RFI filter.
EN50081-1*, EN500821-2 and EN50081-3 first environment with optional RFI filter. *Size 1 only |
|
AC Supply Requirements |
| Voltage |
200V model: 200 to 240 VAC +10%
400V model: 380 to 480 VAC +10% |
| Phase |
1Ø and 3Ø (Model Dependent) |
Maximum Supply
Imbalance |
2% negative phase sequence (3% voltage imbalance between phases) |
| Frequency |
48 to 62 Hz |
Input Displacement
Power Factor |
0.97 |
|
Control |
| Carrier Frequency |
3, 6 and 12 kHz (Default Value Model Dependent) |
| Output Frequency |
Up to 1000 Hz |
| Frequency Accuracy |
+0.01% of full scale |
| Frequency Resolution |
0.1 Hz |
| Analog Input Resolution |
10 Bit + sign (Qty 2) |
| Serial Communications |
ANSI 2-wire EIA485 via RJ45 connector.
Baud rate is 4800, 9600 or 19,200 |
| Braking |
DC injection braking standard. Dynamic braking transistor standard (not available on Size 1). |
|
Protection |
DC Bus
Undervoltage Trip |
200V model 180 VDC
(approximately 127 VAC line voltage)
400V model: 400 VDC
(approximately 282 VAC line voltage) |
DC Bus
Overvoltage Trip |
200V model: 420 VDC
(approximately 299 VAC line voltage)
400V model: 830 VDC
(approximately 587 VAC line voltage) |
MOV Voltage
Transient Protection |
160 Joules, 1400 VDC clamping
(Line to line and line to ground) |
| Drive Overload Trip |
Current overload value is exceeded. Programmable to allow up to 150% of drive current for one minute. |
Instantaneous
Overcurrent Trip |
215% of drive rated current |
| Phase Loss Trip |
DC bus ripple threshold exceeded |
| Overtemperature Trip |
Drive heatsink temperature exceeds 95°C (203°F) |
| Short Circuit Trip |
Protects against output phase to phase fault |
| Ground Fault Trip |
Protects against output phase to ground fault |
| Motor Thermal Trip |
Electronically protects the motor from overheating due to loading conditions |
|
Approvals & Listings |
| UL, cUL |
UL File #E171230 |
| IEC |
Meets IEC Vibration, Mechanical Shock and Electromagnetic Immunity Standards |
| CE |
Designed for marking |
| NEMA |
NEMA 1 enclosure type |
| ISO 9002 |
Certified Manufacturing Facility |