TERMINAL DIAGRAM

Control Techniques Commander SE Terminal Diagram

NOTE

1

Thermal protection required. Not available on Commander SE Size 1

2

Not used for single-phase input

3

Some I/O may be modified via drive
Keypad. Enhanced configuration may be done using SESoft or the optional Universal Keypad.

For complete instructions, refer to the Commander SE User Guide available from local supplier or controltechniques.

Programmable Analog
Programmable Digital 
Non-Programmable
TERMINAL DESCRIPTION
Pin#Function*Type/Description Notes
10V CommonCommon for External Analog Signals
2Analog Input 1
(Local frequency / Speed Reference), 10 bit
Single-ended
Analog Input
0 to +10 VDC,
100k Ohms,
Sample time 6ms
3+10 VDC User SupplyReference Supply5 mA max
Short Circuit Protected
40V CommonCommon for External Digital Signals
5Analog Input 2
(Remote frequency / Speed Reference), 10 bit
Single-ended
Analog Input
4-20mA** Input,
200 Ohms,
Sample Time 6ms
6Analog Output 1
(Frequency / Speed), 10 bit
Single-ended
Analog Output
Unipolar
0 to +10 VDC
@ 5 mA max
Update Time 22ms
7+24 VDC User SupplyUser Supply100 mA max
Short Circuit Protected
8Digital I/O 1
(Zero Speed Output)
Digital
Input / Output
0 to 24 VDC,
7.5k Ohms input or
0 to 24 VDC,
50 mA max output
Update Time 1.5ms
9Digital Input
(Enable)
Digital Input0 to 24 VDC,
7.5k Ohms
Update Time 1.5ms
10Digital Input
(Run Forward)
Digital Input0 to 24 VDC,
7.5k Ohms
Update Time 1.5ms
11Digital Input
(Run Reverse)
Digital Input0 to 24 VDC,
7.5k Ohms
Update Time 1.5ms
12Digital Input
(Local / Remote Select)
Digital Input0 to 24 VDC,
7.5k Ohms
Update Time 1.5ms
13Digital Input
(Jog Select)
Digital Input0 to 24 VDC,
7.5k Ohms
Update Time 1.5ms
14+24 VDC User SupplyUser Supply100 mA max
Short Circuit Protected
15Status Relay (Drive Healthy)Normally Open240 VAC, 6A resistive
16Status Relay (Drive Healthy)Normally Open240 VAC, 6A resistive
Programmable AnalogProgrammable Digital

All Analog I/O is scalable

* Values in parenthesis designate default functions.
** 0-20, 20-0, and 20-4 mA are also available. See Commander SE Manual.

Information provided by Control Techniques, a world leader in the design, production and marketing of electronic drives for the control of electric motors.

Print Friendly, PDF & Email