Input Connection |
|
Input Voltage (U1) |
208/220/230/240 VAC 3-phase +/-10% for 200 VAC units 380/400/415/440/460/480/500
VAC 3-phase +/-10% for
480 VAC units |
|
Input Frequency |
48 to 63 Hz, maximum rate of change 17%/second |
|
Line Imbalance |
Max +/-3% of nominal phase to phase input voltage |
|
Fundamental Power Factor (cosØ) Connection |
0.98 (at nominal load) |
|
|
|
|
Output Connection |
|
Output Voltage |
0 to U1 3-phase symmetrical, UN at the field weakening point |
|
Output Frequency |
-300 to +300 Hz, in DTC mode (0-3.2((U1 input
voltage/UN motor)*fN motor)) |
|
Frequency Resolution |
0.01 Hz |
|
Continuous Current |
1.0 * I2N (normal use)
1.0 * I2hd (heavy-duty use) |
|
Short Term Overload Capacity |
INmax = 1.1 * I2N (1 min /5 minutes @ 40°C), typical
INhdmax = 1.5 * I2hd (at least 1 min / 5 min @ 40°C)
|
|
Peak Overload Capacity |
1max (400 VAC and 500 VAC) (at least 10 seconds at start) |
|
Field Weakening Point |
8 to 300 Hz |
|
Switching Frequency |
3 kHz (average) |
|
Acceleration Time |
0 to 1800 s |
|
Deceleration Time |
0 to 1800 s |
|
Efficiency |
98% at nominal power level |
|
Short Circuit Withstand Rating |
65,000 AIC (UL) R2-R8 |
|
Connection |
U2, V2, W2 |
|
Ambient Conditions, Operation |
|
Air Temperature |
0° to 40°C (104°F), above 40°C the maximum output current is de-rated 1% for every additional 1°C
(up to 50°C (122°F) maximum limit) |
|
Relative Humidity |
5 to 95%, no condensation allowed, maximum relative humidity is 60% in the presence of corrosive gasses |
|
Contamination Levels |
|
|
|
IEC |
60721-3-1,60721-3-2 and 60721-3-3 |
|
|
Chemical Gasses |
3C1 (w/o coating), 3C2 (with coating)
|
|
|
Solid Particles |
3S2 |
|
Installation Site Altitude |
0 to 1000 m (3300 ft) above sea level. At sites over 1000 m above sea level, the maximum power is de-rated 1 % for
every additional 1 00 m (330 ft). If the installation site is higher than 2000 m above sea level, please contact your
local ABB distributor or representative for further information. |
|
Vibration |
Max 1 mm (0.04") 5 to 13.2 Hz, Max 7 m/s2 (23
ft/s2) 13.2 to 100 Hz sinusoidal |
|
Ambient Conditions, Storage |
|
Air Temperature
|
-20° to 70°C (-4 ° to 158°F)
|
|
Relative Humidity |
Less than 95%, no condensation allowed |
|
Atmospheric Pressure
|
70 to 106 kPa (10.2 to 15.4 PSI)
|
|
Vibration |
Max 1 mm (0.04") 5 to 13.2 Hz, Max 7 m/s2 (23 ft/s2) 13.2 to 100 Hz |
|
Shock (IEC 60068-2-29)
|
Max 100 m/s2 (330 ft/s2) 11 ms
|
|
Ambient Conditions, Transportation |
|
Air Temperature
|
-20 to 70 C (-4 to 158 F)
|
|
Relative Humidity |
Max 95% |
|
Atmospheric Pressure
|
60 to 106 kPa (8.7 to 15.4 PSI)
|
|
Vibration |
Max 3.5 mm (0.14") 2 to 9 Hz, Max 15 m/s2 (49 ft/s2) 9 to 200 Hz sinusoidal |
|
Shock (IEC 60068-2-29)
|
Max 100 m/s2 (330 ft/s2) 11 ms
|
|
Free Fall |
250 mm (weight under 100 kg)
100 mm (weight over 100 kg) |
|
Cooling Information |
|
Cooling Method
|
Internal Fan
|
|
Power Loss |
Approximately 3% of rated power |
|
Auxiliary Power Supply |
|
Voltage
|
24 VDC, +/- 10%
|
|
Maximum Current |
250 mA |
|
Protection
|
Short Circuit Protection
|
|
Terminal Block Size |
0.3 to 3 mm2 (12 to 22 AWG) |
|
Analog Inputs |
|
Two Programmable Differential Current Inputs
|
|
|
Signal Level |
0 (4) to 20mA |
|
|
Input Resistance
|
R1 = 100 ohms
|
|
One Programmable Differential Voltage Input |
|
|
Signal Level
|
-10 VDC 0 (2) VDC to +10 VDC
|
|
|
Input Resistance |
R1 = 200 k-ohms |
|
Common Mode Voltage
|
+/-15 VDC, max.
|
|
Common Mode Rejection Ratio |
> 60 dB at 50 Hz |
|
Resolution
|
0.025% (12 bit)
|
|
Accuracy +/- 0.5% |
|
|
Input Updating Time
|
6 ms (Standard Application Software)
|
|
Terminal Block Size |
Cables 0.3 to 3.3 mm2 (12 to 22 AWG) |
|
Optional Isolation
|
Available through
external Module
|
|
Reference Power Supply |
|
Voltage
|
+10 VDC, 0, -10 VDC +/- 0.5% at 25 C (77 F)
|
|
Maximum Load |
10mA |
|
Applicable Potentiometer
|
1 k-ohm to 10 k-ohm
|
|
Terminal Block Size |
Cables 0.3 to 3.3 mm2 (12 to 22 AWG) |
|
Analog Outputs |
|
Two Programmable Current Outputs
|
|
|
Signal Level |
0 (4) to 20 mA |
|
|
Resolution
|
0.025% (12 bit)
|
|
|
Accuracy |
+/-1% Full Scale Range) at 25 C (77 F), temperature coefficient +/- 200 ppm/C (+/- 111
ppm/F) max. |
|
|
Maximum Load Impedance
|
700 ohms
|
|
|
Output Updating Time |
24 ms, max |
|
|
Terminal Block Sizes
|
Cables 0.3 to 3.3 mm2 (12 to 22 AWG)
|
|
Digital Inputs |
|
Six Programmable Digital Inputs (Common Ground), plus One Start Interlock
|
|
|
Isolation |
Isolated, can be divided in two isolated groups |
|
|
Isolation Test Voltage
|
500 VAC, 1 minute
|
|
|
Terminal Block Size |
Cables 0.3 to 3.3 mm2 (12 to 22 AWG) |
|
|
Signal Level
|
24 VDC, -15% to +20%
|
|
|
Logical Thresholds |
< 8 VDC at "0", >12 VDC at "1" |
|
|
Input Current
|
10 mA, Digital Input 1 to Digital Input 5, 5 mA Digital Input 6
|
|
|
Filtering Time Constant |
1 ms |
|
|
Input Updating Time
|
6 ms
|
|
Internal 24 VDC Supply for Digital Inputs |
|
|
Voltage
|
24 VDC
|
|
|
Maximum Current |
100 mA |
|
|
Connector
|
X22:7
|
|
|
Protection |
Short Circuit Proof |
|
An external 24 VDC supply may be used instead of the internal supply
|
|
Relay Outputs |
|
Three Programmable Relay Outputs
|
|
|
Switching Capacity |
8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC |
|
|
Maximum Continuous Current
|
Ic = 2 A RMS
|
|
|
Contact Material |
Silver Cadmium Oxide (AgCdO) |
|
|
Isolation Test Voltage
|
4 kVAC, 1 minute
|
|
|
Terminal Block Size |
Cables 0.3 to 3.3 mm2 (12 to 22 AWG) |
|
|
Output Updating Time
|
100 ms
|
|
Protections |
|
Single Phase
|
Protected (input & output)
|
|
Overvoltage Trip Limit |
1.3 * V1max |
|
Undervoltage Trip Limit
|
0.65 * V1min
|
|
Overtemperature |
140°C (284°F) |
|
Auxiliary Voltage
|
Short Circuit Protected
|
|
Ground Fault |
Protected |
|
Microprocessor Fault
|
Protected
|
|
Motor Stall Protection |
Protected |
|
Motor Overtemperature Protection (I2t)
|
Protected
|