POWER SUPPLY |
Voltage |
Three-phase: |
220 - 230 V: 220 / 230 V (+10%, -15%) - 1 ø up
to 3HP without de-rating |
| 380 - 480 V: 380 / 400 / 415 / 440 / 460 / 480 V (+10%,
-15%) |
| Frequency |
50 / 60 Hz +/- 2 Hz (48... 62 Hz) |
| Phase Unbalance |
Up to 3% |
| Cos (Displacement Power Factor |
Greater than 0.98 |
| ENCLOSURE |
Degree of Protection |
NEMA 1 / IP 20 (Sizes 1 to 8) |
| IP 20 (Sizes 9 and 10) |
| Finishing Color |
Plastic Cover - Light Gray PANTONE 413 C (sizes 1 and
2) |
| Metallic Cover and Sides - Light Gray RAL 7032 (sizes
3 to 10) |
| Base - Dark Gray RAL 7022 (sizes 3 to 10) |
| CONTROL |
Power Supply |
Switched Mode Power Supply Fed from the DC Link |
| Microprocessor |
32 bit RISC Technology |
| PWM Technique |
SVM Sine wave PWM (Space Vector Modulation) |
| Software Implemented Current, Flux and Speed Regulators
(Full Digital) |
| Control Modes |
Scalar (Voltage Source - V / F) |
| Sensorless Vector (without encoder) |
| Flux Vector with Encoder |
| Switching Frequency |
1.25 / 2.5 / 5.0 / 10 kHz |
| Frequency Range |
0... 204 Hz for V /F and Vector with Encoder Control
(60 Hz Motor) |
| 0... 170 Hz for V /F and Vector with Encoder Control
(50 Hz Motor) |
| 0... 100 Hz for Sensorless Vector Control (50 or 60 Hz
Motor) |
| Overload Capacity |
150% for 60 seconds, every 10 minutes |
| 180% for 1 second every 10 minutes |
| Efficiency |
Greater than 97% |
| PERFORMANCE |
Speed Control |
V / F Mode |
Regulation (with Slip Compensation) : 1% of Motor Rated
Speed |
| Resolution: 1 rpm (Keypad Reference) |
| Speed Regulation Range: 20:1 |
Sensorless
Vector Mode |
Regulation: 0.5% of Motor Rated Speed |
| Resolution: 1 rpm (Keypad Reference) |
| Range: 100:1 |
Flux
Vector Mode
with Encoder |
Regulation with: |
| 10 bit Analog Reference: +/- 0.1% of Motor Rated Speed |
| 14 bit Analog Reference: +/- 0.01% of Motor Rated Speed
* |
| Digital Reference (Ex: Keypad or Serial): +/- 0.01% of
Motor Rated
Speed |
| Range: Down to 0 rpm |
| Torque Control |
Flux Vector
Modes |
Regulation: +/- 10% of Motor Rated Torque |
| Range: 0... 150% of Motor Rated Torque |
| CONTROL INPUTS |
Analog |
2 Programmable Differential Inputs (10 bit): 0...10
V, 0...20 mA or 4...20 mA |
| 1 Programmable Bipolar Input (14 bit): -10... +10 V,
0...20 mA or 4...20 mA * |
| 1 Programmable Isolated Input (10 bit): 0... 10 V, 0...20
mA or 4...20 mA * |
| Digital |
6 Programmable Isolated Input: 24 Vdc |
| 1 Programmable Isolated Input: 24 Vdc * |
| 1 Programmable Isolated Input: 24 Vdc (for Motor PTC
Thermistor) * |
| Encoder |
1 Differential Input, with 12 Vdc Internal Isolated Power
Supply (14 bit
resolution) * |
| CONTROL OUTPUTS |
Analog |
2 Programmable Outputs (11 bit): 0... 10 V |
| 2 Programmable Bipolar Outputs (14 bit): -10... +10 V
* |
| 2 Programmable Isolated Outputs (11 bit): 0... 20 mA
or 4... 20 mA * |
| Relay |
2 Programmable Outputs, Form C Contacts (NO/NC): 240
Vac, 1 A |
| 1 Programmable Output, Form A Contact (NO): 240 Vac,
1 A |
| Transistor |
2 Programmable Isolated Outputs (Open Collector): 24
Vdc, 50 mA * |
| Encoder |
1 Isolated Differential Encoder Signals Output: 5...
15 Vdc External Power
Supply * |
| COMMUNICATION |
Serial |
RS-232 with KCS-CFW09 Kit * |
| RS-485, Isolated, with EBA, EBE or EBB Board * |
| Field Bus |
Profibus DP, DeviceNet or Modbus RTU, with KFB kits * |
SAFETY |
Protections |
DC Link Over Voltage |
Output Short Circuit |
| DC Link Under Voltage |
Output Ground Fault |
| VFD Over Temperature |
External Fault |
| Motor Over Temperature * |
Self-diagnosis Fault |
| Output Over Current |
Programming Error |
| Motor Overload (i x t) |
Serial Communication Fault |
| Dynamic Braking Resistor Overload |
Motor or Encoder Connection Fault |
| CPU / EPROM Error (Watchdog) |
Power Supplv Phase Fault (30 A and above models) |
| Encoder Fault |
Keypad Connection Fault |
| AMBIENT |
Temperature |
0... 104°F (40°C), up to 122°F (50°C)
with 2% / °C Output
Current De-rating |
| Humidity |
5 ... 90% Non Condensing |
| Altitude |
0... 3300 ft (1000 m) (up to 13100 ft 4000 m with 10%
/ 1000 m Output
Current De-rating |
| CONFORMITIES |
EMC Directive 89/336/
EEC EN 61800-3
|
Electromagnetic Compatibility - Industrial
Environment
EMC - Emission and Immunity
|
| LVD 73/23/EEC |
Low Voltage Directive |
| IEC 146 |
Semiconductor Inverters |
| UL 508C |
Power Conversion Equipment |
| EN 50178 |
Electronic Equipment for Use in Power Installations |
| EN 61010 |
Safety Requirements for Electrical Equipment for Measurement,
Control
and Laboratory Use |
| CERTIFICATIONS |
UL (USA) and
cUL (CANADA) |
Underwriters Laboratories Inc. USA |
| CE (EUROPE) |
Phoenix Test - Labs GmbH - Germany |
Data subject to change without previous notice.
* 0ptional