Call Toll Free (866) 492-9888
|
Joliet Technologies is proud to be an integrator of Soft Starter
Products by SOLCON.
RVS-DN
Digital Soft Starter with Advanced Motor Protection
Digital soft starter with advanced motor protection. Incorporates unique features
such as pump control, energy save, slow speed with electronic reversing. Range:
8-3500A, 4-3000 KW, 220-1000V. Key features include: easy to install and use,
rugged design for working in harsh conditions, 3rd generation processor technology,
and a choice of six sizes.
Motor Protection: RVS DN
Motor Protection Enchanced, Full Featured, Microprocessor-Based, for
Motors 4-3500A, 4-3000KW, 208-1000V
To see examples of these soft starters in demanding conditions check out our
Naval, Marine, Industial, Oil and Gas examples of Solcon soft starters in a
variety of applications
- Maximum Motor Protection
- Eliminates high inrush current and damaging mechanical shock
- Third generation microprocessor circuitry
- Heavy duty design: 50°C ambient temperature
- Soft, stepless acceleration & deceleration
- Power factor capacitors can be connected directly to the upstream contactor
- Unique starting & stopping characteristics (special characteristics
for Ex motors)
- Sophisticated motor protection package
- User friendly, easy installation and operation
- RS485 Communication with MODBUS, PROFIBUS or MODBUS/TCP protocols (others
available on request)
- Wide 45-65Hz Auto-tracking frequency range combining special software with
unique hardware arrangement allowing starting and stopping while the frequency
variates (designed for Marine, Offshore and Generators operating under continuous
frequency variation
Motor Protection - Advanced Starting and Stopping Characteristics of RVS-DN
- Reduced inrush current & mechanical shock
- Soft, smooth stepless acceleration & deceleration
- Unique features such as: Pump Control Program, Dual Adjustment, Slow Speed
with Electronic Reversing, Energy Save, etc.
- Torque and current starting & stopping characteristics
Sophisticated Motor Protection – RVS-DN
- Many starts & start
inhibit greatly improve motor protection.
- Long start time (Stall protection)
- Electronic shear-pin (Jam) with adjustable curves and delay
- Electronic overload with selectable curves
- Under current with programmable auto reset
- Phase loss
- Phase sequence and Under/Over frequency
- Under/Over voltage with programmable auto reset
- Load loss (broken drive belt)
- External fault
- Shorted SCR
- Starter over temperature protection
- Motor insulation test (option)
- Motor thermistor (option)
- When using "Preparation for Bypass" all protective functions
remain active
RVS-DN Control
- All inputs & outputs are isolated.
- Three C/O output relays.
- Thermistor input.
- Analogue output.
- Communication RS 485 with MODBUS RTU or MODBUS Plus protocols.
- User friendly keypad interface allowing precise settings.
- Bright LEDs for immediate visual interface.
- Interactive and informative 4 language LCD for easy trouble shooting.
- Statistical data.
- Motor insulation protection.
- Hardware and software integration to allow starting from diesel-generator
RVSDN Construction
- Heavy duty fully rated design (ambient 50°C).
- Compact, light weight.
- Cost efficient plug-in control module, identical for sizes B-G.
- Preparation for bypass contactor (option), maintaining protection even
after bypass closes.
RVS-DN with Motor Protection Features Typical Applications
- Pumps (Water
utilities, Industry)
- Compressors
- Conveyors & monorails
- Mixers & Agitators
- Fans & Centrifuges
- Hydraulic pumps
- Starting from weak Mains supply
- Marine (Thrusters, pumps, fans, refrigeration, compressors, etc..)
RVS-DN Soft Starter
Starter
Type |
Motor KW
V~ +10% : -15% |
Motor HP
V~ +10% : -15% |
Starter
Size
A-G |
Dimensions (mm) & Weight |
230V |
380-440V |
500V |
690V |
230V |
460V |
575V |
W |
H |
D |
Kg |
RVS-DN 8 |
2.2 |
4 |
5.5 |
7.5 |
3 |
5 |
7.5 |
A |
153 |
310 |
170 |
5 |
RVS-DN 17 |
4 |
7.5 |
11 |
15 |
5 |
10 |
15 |
153 |
310 |
170 |
5 |
RVS-DN 31 |
7.5 |
15 |
16.5 |
22 |
10 |
20 |
30 |
153 |
310 |
217 |
7 |
RVS-DN 44 |
11 |
22 |
30 |
37 |
15 |
30 |
40 |
153 |
310 |
217 |
8 |
RVS-DN 58 |
15 |
30 |
37 |
45 |
20 |
40 |
50 |
153 |
310 |
217 |
8 |
RVS-DN 72 |
18.5 |
37 |
45 |
55 |
25 |
50 |
60 |
153 |
310 |
217 |
8 |
RVS-DN 85 |
22 |
45 |
55 |
65 |
30 |
60 |
75 |
B |
274 |
370 |
279 |
15 |
RVS-DN 105 |
30 |
55 |
75 |
90 |
40 |
75 |
100 |
274 |
370 |
279 |
15 |
RVS-DN 145 |
37 |
75 |
90 |
132 |
50 |
100 |
125 |
274 |
370 |
279 |
15 |
RVS-DN 170 |
45 |
90 |
110 |
160 |
60 |
125 |
150 |
274 |
370 |
279 |
15 |
RVS-DN 210 |
55 |
110 |
132 |
185 |
75 |
150 |
200 |
C |
590 |
500 |
275 |
45 |
RVS-DN 310 |
90 |
160 |
220 |
250 |
100 |
200 |
300 |
590 |
500 |
275 |
45 |
RVS-DN 390 |
110 |
200 |
250 |
315 |
125 |
250 |
350 |
590 |
500 |
275 |
45 |
RVS-DN 460 |
132 |
250 |
315 |
450 |
150 |
300 |
400 |
D |
623 |
660 |
290 |
65 |
RVS-DN 580 |
160 |
315 |
400 |
500 |
200 |
400 |
500 |
623 |
660 |
290 |
65 |
RVS-DN 820 |
250 |
450 |
600 |
750 |
300 |
600 |
700 |
623 |
660 |
290 |
65 |
RVS-DN 950 |
295 |
500 |
670 |
925 |
400 |
815 |
1030 |
623 |
662 |
290 |
83.5 |
RVS-DN 1100 |
355 |
630 |
800 |
1000 |
400 |
800 |
1000 |
E |
723 |
1100 |
370 |
170 |
RVS-DN 1400 |
400 |
800 |
900 |
1300 |
500 |
1000 |
1250 |
723 |
1100 |
370 |
170 |
RVS-DN 1800 |
560 |
950 |
1250 |
1500 |
600 |
1250 |
1500 |
723 |
1100 |
370 |
170 |
RVS-DN 2150 |
NA |
1250 |
1500 |
2000 |
700 |
1500 |
2000 |
F |
750 |
1300 |
392 |
235 |
RVS-DN 2400 |
NA |
1400 |
1750 |
2250 |
800 |
1750 |
2250 |
G |
900 |
1300 |
360 |
350 |
RVS-DN 2700 |
NA |
1550 |
2000 |
2500 |
900 |
2000 |
2500 |
900 |
1300 |
360 |
350 |

* Type test (DNV is type approved as of April 2006)
Notes:
- RVS-DN 8 through RVS-DN 820 are UL & cUL Approved
- RVS-DN 1100 and above
are designed to meet UL & cUL requirements
- Contact us for RVS-DN 210,
310, 390, 460, 580, 820 & 950 Slim version
(Narrow)
- Select the starter according to motor's Full Load Ampere (FLA) -
as indicated on its nameplate (even if the motor is not fully loaded)
- The selection table above, concerns standard, 1500 R.P.M. 50Hz, three-phase
asynchronous motors. These values are given for guidance and may vary according
to individual motor manufacturers (as well as number of poles)
- It is the user’s responsibility to verify that motor’s FLA does
not exceed Starter’s FLC
|