Design and Mode of Operation
Closed-loop functions in field circuit
EMFcontroller
The EMF controller compares the EMF (induced motor voltage) setpoint and actual value
and specifies the setpoint for the field current controller, providing an EMF-dependent
closed-loop field-weakening control. The EMF controller operates as a PI controller, the
P and I components can be set independently of one another. The controller can also
be operated as a pure P or pure I controller. A feedforward control operates in parallel
to the EMF controller. This applies feedforward control as a function of speed to the field
current setpoint by means of an automatically recorded field characteristic (see
optimization runs). An adding point is located after the EMF controller, at which
additional field current setpoints can be entered via a connector, e.g. analog input or
serial interface. The limitation for the field current setpoint is then applied (maximum
and minimum setpoint limits can be set independently of one another). The limitation is
implemented via a parameter or connector, in which case the minimum is applied as
the upper limit and the maximum for the lower limit.
Field-current controller
The current controller for the field is a PI controller with independent settings for Kp
and Tn. It can also be operated as a pure P or pure I controller. A feedforward control
operates in parallel to the field current controller. This calculates and sets the firing
angle for the field circuit as a function of current setpoint and line voltage. The
feedforward control supports the current controller and ensures a good dynamic response in the field circuit.
Gating unit
The gating unit generates the gate pulses for the power section thyristors in
synchronism with the line voltage in the field circuit. Synchronization is measured on
the power section and is not therefore dependent on the electronics supply. The gate
pulse position timing is determined by the output values of the current controller and
feedforward control. The firing angle setting limit can be set in a parameter. The gating
unit is automatically adjusted to the connected line frequency within a frequency range
of 45 to 55 Hz.