Environment |
| Ambient Operating Temperature |
0° to 40°C (32° to 104°F)
0° to 50°C (32° to 122°F) with derating |
| Cooling method |
Forced convection |
| Humidity |
95% maximum non-condensing at 40°C (104°F) |
| Storage Temperature |
-40° to 50°C (-40° to 140°F) |
| Altitude |
0 to 3000m (9,900 ft). Derate 1% per 100m (328
ft) between 1000m (3280 ft) and 3000m (9,900 ft). |
| Vibration |
Tested in accordance with IEC 68-2-34 |
| Mechanical Shock |
In accordance with IEC 68-2-27 |
| Enclosure |
NEMA 1 (IP 21), NEMA 12 (IP 54) through panel
mounting |
Electromagnetic
Immunity |
In compliance with IEC801 and
EN50082-2, and complies with EN61800-3 with built-in filter |
Electromagnetic
Emissions |
In compliance with EN50081-2 when the recommended
RFI filter is used and EMC installation guidelines are followed |
|
AC Supply Requirements |
| Voltage |
200 to 240 VAC +10%
380 to 480 VAC +10%
500 to 575 VAC +10%
500 to 690 VAC +10% |
| Phase |
3Ø |
| Phase
Imbalance Tolerance |
2% negative phase sequence (equivalent to 3%
voltage imbalance between phases) |
| Frequency |
48 to 65 Hz |
Input Displacement
Power Factor |
0.93 |
|
Control |
| Carrier Frequency |
3, 4, 6, 8, 12, 16kHz |
| Output Frequency |
0 to 3000Hz (Open loop) |
| Output Speed |
0 to 40,000 RPM (Closed loop) |
| Frequency Accuracy |
+0.01% of full scale |
| Frequency Resolution |
0.001 Hz |
| Analog Input Resolution |
10 Bit + sign (Qty 2); 16 Bit + sign (Qty 1) |
| Serial Communications |
2 or 4-wire RS485.
Protocol is
ANSI x 3.28-2.5-A4, or Modbus RTU Baud rate 300 to 115,200. |
| Braking |
DC injection braking (stopping and holding)
standard. Dynamic braking transistor standard. |
Control Power
Ride Through |
Up to 1 second depending on inertia and decel time |
|
Protection |
DC Bus
Undervoltage Trip |
175 / 350 / 435 VDC
(approximately 124 / 247 / 307 VAC line voltage) |
DC Bus
Overvoltage Trip |
415 / 830 / 990 VDC
(approximately 293 / 587 / 700 VAC line voltage) |
MOV Voltage
Transient Protection |
160 Joules, 1400 VDC clamping
(Line to line and line to ground) |
| Drive Overload Trip |
Current overload value is exceeded. Programmable
for Normal Duty or Heavy Duty.
Open loop or Closed loop operation. |
Instantaneous
Overcurrent Trip |
225% of drive rated current |
| Phase Loss Trip |
DC bus ripple threshold exceeded |
| Overtemperature Trip |
Drive heatsink, cntrol board, and option module(s)
mounting |
| Short Circuit Trip |
Protects against output phase to phase fault |
| Ground Fault Trip |
Protects against output phase to ground fault |
| Motor Thermal Trip |
Electronically protects the motor from overheating due to loading conditions |
|
Approvals & Listings |
| UL, cUL |
UL File #E171230 |
| IEC |
Meets IEC Vibration, Mechanical Shock and Electromagnetic Immunity Standards |
| CE |
Designed for marking |
| NEMA |
NEMA 1 enclosure type |
| VDE |
Meets VDE Electromagnetic Emissions Standards |
| ISO 9002 |
Certified Manufacturing Facility |
For through-panel mounting dimensions or dimensions of size 6, 7,