ABB
General Machinery Drives
ACS350, 0.5hp to 10hp Technical Guide
Technical data
| Cooling |
The ACS350 is configured with cooling fans as standard. The cooling air must be free from corrosive materials and must not be above the maximum ambient temperature of 40°C (50°C with derating). For more specific limits see the Technical specification - Environmental limits in this catalog. |
Cooling air flow
| Type Code |
Frame
Size |
Heat Dissipation
|
Air Flow |
|
W
|
BTU/Hr |
m3/h |
ft3/min |
|
1-phase supply voltage 200 - 240 V units |
| ACS350-01U-02A4-2 |
R0 |
25 |
85 |
-* |
-* |
| ACS350-01U-04A7-2 |
R1 |
46 |
157 |
24 |
14 |
| ACS350-01U-06A7-2 |
R1 |
71 |
242 |
24 |
14 |
| ACS350-01U-07A5-2 |
R2 |
73 |
249 |
21 |
12 |
| ACS350-01U-09A8-2 |
R2 |
96 |
328 |
21 |
12 |
|
3-phase supply voltage 200 - 240 V units |
| ACS350-03U-02A4-2 |
R0 |
19 |
65 |
-* |
-* |
| ACS350-03U-03A5-2 |
R0 |
31 |
106 |
-* |
-* |
| ACS350-03U-04A7-2 |
R1 |
38 |
130 |
24 |
14 |
| ACS350-03U-06A7-2 |
R1 |
60 |
205 |
24 |
14 |
| ACS350-03U-07A5-2 |
R1 |
62 |
212 |
21 |
12 |
| ACS350-03U-09A8-2 |
R2 |
83 |
283 |
21 |
12 |
| ACS350-03U-17A6-2 |
R2 |
152 |
519 |
52 |
31 |
|
3-phase supply voltage 380 - 480 V units |
| ACS350-03U-01A2-4 |
R0 |
11 |
38 |
-* |
-* |
| ACS350-03U-01A9-4 |
R0 |
16 |
55 |
-* |
-* |
| ACS350-03U-02A4-4 |
R0 |
21 |
72 |
-* |
-* |
| ACS350-03U-03A3-4 |
R1 |
31 |
106 |
13 |
8 |
| ACS350-03U-04A1-4 |
R1 |
40 |
137 |
13 |
8 |
| ACS350-03U-05A6-4 |
R1 |
61 |
208 |
19 |
11 |
| ACS350-03U-08A8-4 |
R1 |
94 |
321 |
24 |
14 |
| ACS350-03U-12A5-4 |
R3 |
130 |
444 |
52 |
31 |
| ACS350-03U-15A6-4 |
R3 |
173 |
591 |
52 |
31 |
| * According to IEC-60269 standard. |
Free space requirements
| Enclosure Type |
Space Above
mm/in |
Space Below
mm/in |
Space on Left/Right
mm/in |
| All Frame Sizes |
80/3.15 |
80/3.15 |
0/0 |
| Fuses |
Standard semi-conductor fuses can be used with the ACS350. Recommended fuse
ratings are show in the table below. |
Selection table
| Type Code |
Frame
Size |
IEC Fuses
|
UL Fuses |
|
A
|
Fuse
Type* |
A |
Fuse
Type* |
|
1-phase supply voltage 200 - 240 V units |
| ACS350-01U-02A4-2 |
R0 |
10 |
gG |
10 |
UL class T |
| ACS350-01U-04A7-2 |
R1 |
16 |
gG |
20 |
UL class T |
| ACS350-01U-06A7-2 |
R1 |
20 |
gG |
25 |
UL class T |
| ACS350-01U-07A5-2 |
R2 |
25 |
gG |
30 |
UL class T |
| ACS350-01U-09A8-2 |
R2 |
35 |
gG |
35 |
UL class T |
|
3-phase supply voltage 200 - 240 V units |
| ACS350-03U-02A4-2 |
R0 |
10 |
gG |
10 |
UL class T |
| ACS350-03U-03A5-2 |
R0 |
10 |
gG |
10 |
UL class T |
| ACS350-03U-04A7-2 |
R1 |
10 |
gG |
15 |
UL class T |
| ACS350-03U-06A7-2 |
R1 |
16 |
gG |
15 |
UL class T |
| ACS350-03U-07A5-2 |
R1 |
16 |
gG |
15 |
UL class T |
| ACS350-03U-09A8-2 |
R2 |
16 |
gG |
20 |
UL class T |
| ACS350-03U-17A6-2 |
R2 |
25 |
gG |
35 |
UL class T |
|
3-phase supply voltage 380 - 480 V units |
| ACS350-03U-01A2-4 |
R0 |
10 |
gG |
10 |
UL class T |
| ACS350-03U-01A9-4 |
R0 |
10 |
gG |
10 |
UL class T |
| ACS350-03U-02A4-4 |
R0 |
10 |
gG |
10 |
UL class T |
| ACS350-03U-03A3-4 |
R1 |
10 |
gG |
10 |
UL class T |
| ACS350-03U-04A1-4 |
R1 |
16 |
gG |
15 |
UL class T |
| ACS350-03U-05A6-4 |
R1 |
16 |
gG |
15 |
UL class T |
| ACS350-03U-08A8-4 |
R1 |
20 |
gG |
25 |
UL class T |
| ACS350-03U-12A5-4 |
R3 |
25 |
gG |
30 |
UL class T |
| ACS350-03U-15A6-4 |
R3 |
30 |
gG |
35 |
UL class T |
| * According to IEC-60269 standard. |
© 2006 ABB Inc. ACS350-PHTC01U-EN REV B, Effective: 1/1/06.
Specifications subject to change