Input connection |
| Voltage and power range |
1-phase, 200 to 240 V +10%
0.37 to 2.2 kW (0.5 to 3 hp)
3-phase, 200 to 240 V +10%
0.37 to 2.2 kW (0.5 to 3 hp)
3-phase, 380 to 480 V +10%
0.37 to 4 kW (0.5 to 5 hp) |
|
Frequency |
48 to 63 Hz |
| Power factor |
0.98 |
| |
|
Output connection |
|
Voltage |
3-phase, from 0 to Usupply |
| Frequency |
0 to 500 Hz |
Continuous loading
capability
(constant torque at a max. ambient temperature 40°C) |
Rated output current I2N |
Overload capability
(at a max. ambient temperature of
40°C) |
1.5 x I2N for 1 minute every 10 minutes
1.8 x I2N for 2 s every 10 minutes |
Switching frequency
Default
Selectable |
4 kHz
4 to 12 kHz with 4 kHz steps |
|
Acceleration time |
0.1 to 1800 s |
| Deceleration time |
0.1 to 1800 s |
|
Braking |
brake chopper standard (100% braking capability) |
| |
|
Environmental limits |
|
Ambient temperature |
-10 to 40°C (14 to 104°F), no frost allowed,
50°C (122°F) with 10% derating |
Altitude
Output current |
Rated current available at 0 to 1000 m
(0 to 3281 ft) reduced by 1% per 100 m
(328 ft) over 1000 to 2000 m (3281 to 6562 ft) |
|
Relative humidity |
Lower than 95% (without condensation) |
| Protection class |
IP 20 / Protected Chassis |
| Enclosure color |
NCS 1502-Y, RAL 9002, PMS 420 C |
Contamination levels
Transportation
Storage
Operation |
IEC721-3-3
No conductive dust allowed
Class 1C2 (chemical gases)
Class 1S2 (solid particles)
Class 2C2 (chemical gases)
Class 2S2 (solid particles)
Class 3C2 (chemical gases)
Class 3S2 (solid particles) |
| |
|
Programmable control connections |
One analog input
Voltage signal
Current signal
Resolution
Accuracy |
0 (2) to 10 V, Rin > 312 k Ohm
0 (4) to 20 mA, Rin = 100 Ohm
0.1 %
+1% |
| Auxiliary voltage |
24 V DC +10%, max. 200 mA |
Five digital inputs
Input impedance |
12 to 24 V DC with internal or external supply, PNP and NPN, pulse train 0 to 16
kHz.
2.4 k Ohm |
One relay output
Type
Maximum switching voltage
Maximum switching current
Maximum continuous current |
NO + NC
250 V AC/30 V DC
0.5 A/30 V DC; 5 A/230 V AC
2 A rms |
| |
|
Product compliance |
Low voltage Directive 73/23/EEC with supplements
Machinery Directive 98/37/EC
EMC Directive 89/336/EEC with supplements
Quality assurance system ISO 9001
Environmental system ISO 14001
UL, cUL, and CE approvals |
| |
|
EMC (according to EN61800-3) |
|
2nd environment filter, unrestricted distribution with 30 m (98 ft) cable, built-in as standard. |
| |
© 2006 ABB Inc. ACS150-PHTC01U-EN REV B, Effective: 12/1/05.
Specifications subject to change