Input Connection |
Input Voltage (U1)
|
208/220/230/240 VAG 3-phase +10% ... -15%
380/400/415/440/460/480 VAG 3-phase +10% ... -15% |
|
Input Frequency |
48 to 63 Hz |
|
Line Imbalance |
Max +/-3% of nominal phase to phase input voltage |
|
Fundamental Power Factor (cosØ) |
0.98 (at nominal load) |
|
Connection |
U1,V1,W1
|
|
Output Connection |
Output Voltage
|
0 to U1, 3-phase symmetrical, U2 at the field weakening point |
|
Output Frequency |
-500 to +500 Hz |
|
Frequency Resolution |
0.01 Hz |
| Continuous Current |
1.0 * I2N (normal use)
1.0 * I2hd (heavy-duty use) |
|
Short Term Overload Capacity |
1.1 * I2N (1 min/10 min)
1.5 * I2hd (1 min/10 min) |
|
Peak Overload Capacity |
180% of 12hd for 2 seconds each minute |
|
Base Motor Frequency Range |
10 to 500 Hz |
|
Switching Frequency |
1, 4, or 8 kHz |
|
Acceleration Time |
0 to 1800 s |
|
Deceleration Time |
0 to 1800 s |
|
Efficiency |
98% at nominal power level |
|
Short Circuit Withstand Rating |
100,000 AIC |
|
Connection |
U2, V2, W2 |
|
Ambient Conditions, Operation |
|
Air Temperature |
-15° to 40°C (5° to 104°F), no frost allowed, above 40°C the maximum output currents de-rated
1% for every additional 1 °C (up to 50°C (122°F) maximum limit) |
|
Relative Humidity |
5 to 95%, no condensation allowed, maximum relative humidity is 60% in the presence of corrosive gasses |
|
Contamination Levels |
|
|
IEC |
60721-3-1,60721-3-2 and 60721-3-3 |
|
Chemical Gasses |
3C1 and 3C2 |
|
Solid Particles |
3S2 |
| Installation Site Altitude |
0 to 1000 m (3300 ft) above sea level. At sites over 1000 m (3300 ft) above sea level, the maximum power is de-rated 1% for every additional 100 m (330 ft). If the installation
site is higher than 2000 m (6600 ft) above sea level, please contact your local ABB distributor or representative for
further information. |
|
Vibration |
Mechanical conditions Class 3M4 (IEC 60721-3-3)
9...200 Hz 10m/s2 (33 ft/s2)
2...9 Hz 3.0 m (0.12 in) |
|
Ambient Conditions, Storage (in Protective Shipping Package) |
|
Air Temperature |
-40° to 70°C (-40° to 158°F) |
|
Relative Humidity |
Less than 95%, no condensation allowed |
|
Vibration |
In accordance with ISTA 1A and 1 B specifications |
|
Shock (IEC 60068-2-29) |
Max 100 m/s2 (330
ft/s2) 11 ms |
|
Ambient Conditions, Transportation (in Protective Shipping Package) |
|
Air Temperature |
-40° to 70°C (-40° to 158°F) |
|
Relative Humidity |
Max 95% |
|
Atmospheric Pressure |
60 to 106 kPa (8.7 to 15.4 PSI) |
|
Vibration |
In accordance with ISTA 1A and 1 B specifications |
|
Shock (IEC 60068-2-29) |
Max 100 m/s2 (330
ft/s2) 11 ms |
|
Free Fall |
R1: 76 cm (30 in)
R2: 61 cm (24 in)
R3: 46 cm (18 in)
R4: 31 cm (12 in)
R5: 25 cm (10 in)
R6: 15 cm (6 in) |
|
Cooling Information |
|
Cooling Method |
Internal Fan |
|
Power Loss |
Approximately 3% of rated power |
|
Analog Inputs |
|
Two Programmable Inputs |
|
Voltage Reference |
0 (2) to 10 V, 250 kOhm, single ended |
|
Current Reference |
0 (4) to 20 mA, 100 Ohms, single ended |
|
Potentiometer |
10 VDC, 10 mA, 1K to 10 kOhms |
|
Accuracy |
+/- 1 % |
|
Input Updating Time |
12ms |
|
Terminal Block Size |
2.3 mm2 / 14 AWG |
|
Reference Power Supply |
|
Voltage |
+10 VDC, 1% at 25°C (77°F) |
|
Maximum Load |
10mA |
|
Applicable Potentiometer |
1 kOhm to 10 kOhm |
|
Terminal Block Size |
2.3 mm2 / 14 AWG |
|
Analog Outputs |
|
Two Programmable Current Outputs |
|
Signal Level |
0 (4) to 20mA |
|
Accuracy |
+/-1% Full Scale Range at 25°C (77"F) |
|
Maximum Load Impedance |
500 Ohms |
|
Output Updating Time |
TBD |
|
Terminal Block Sizes |
2.3 mm2 / 14 AWG |
|
Digital Inputs |
|
Six Programmable Digital Inputs |
|
Isolation |
Isolated as one group |
|
Terminal Block Size |
2.3 mm2 / 14 AWG |
|
Signal Level |
24 VDC, (10V Logic 0) |
|
Input Current |
15 mA at 24 VDC |
|
Input Updating Time |
TBD |
|
Internal 24 VDC Supply for Digital Inputs |
|
Voltage |
24 VDC, +/-10% |
|
Maximum Current |
250 mA |
|
Protection |
Short Circuit Proof |
|
Relay Outputs |
|
Three Programmable Relay Outputs |
|
Switching Capacity |
8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC |
|
Maximum Continuous Current |
Ic = 2A RMS |
|
Contact Material |
Silver Cadmium Oxide (AgCdO) |
|
Isolation Test Voltage |
4 kVAC, 1 minute |
|
Terminal Block Size |
Cables 0.3 to 3.3 mm2 (12 to 22 AWG) |
|
Output Updating Time |
100 ms |
|
Protections |
|
Single Phase |
Protected (input & output) |
|
Overvoltage Trip Limit |
1.3 * U1nom |
|
Undervoltage Trip Limit |
0.65 * U1nom |
| Overtemperature (IGBT) |
115°C (239°F) |
|
Ground Fault |
Protected |
|
Microprocessor Fault |
Protected |
|
Motor Stall Protection |
Protected |
|
Motor Overtemperature Protection (l2t) |
Protected |
|
|
U1nom = Nominal Line Voltage |
|
Motor / Drive Compatibility |
U1 = lnput Voltage |
|
0.2 < |
IM |
< 2 |
 |
| I2hd |
|
|
U2 = Output Voltage |
| UN = Nominal Motor Voltage |
| fN = Nominal Motor Frequency |
| 12N = Nominal Current - Normal Duty |
| P N = Power - Normal Duty (kW) |
|
0.2 < |
PM |
< 2 |
 |
| PNhd |
|
|
P N = Power - Normal Duty (HP) |
| I2hd = Nominal Current - Heavy-Duty |
| P hd = Power (kW) - Heavy-Duty |
| Phd = Power (HP) -
Heavy-Duty |
| PM = Nominal Motor Power |
|
|
IM = Nominal Motor Current |
© 2004 ABB Inc. All rights reserved Specifications and pricing subject to change
without notice.